Known Issues in GENESIS Version 11 Update 1

The following are known issues in this release.

Known Issues

Reference #

Item

Affected Component

Mitigation / Notes

10357

When running Gmail OAuth support, you must run GmailSample.exe under expanded administrator permissions.

Alert Notifications

 

25424

The client secret is stored in plain text when configuring Gmail OAuth support.

Alert Notifications

This should only be done on a computer where access is restricted to trusted administrators only. Otherwise, that client secret may be misused to access the Gmail account.

 

Connected Field Service alarm triggers occur on alarms having a new alarm time. By default, the version 11 Alarm Server only updates the alarm time when the alarm is acknowledged and returns to normal.

Connected Field Service

The version 11 Alarm Server offers an option, Reset on 'RTN Unack' state (found in the alarm types settings), to change this behavior.

9509

The IoT Subscriber does not communicate through the Proxy.

Internet of Things

This is caused by an upgrade of the NuGet packages, which must be fixed by Microsoft.

 

Trend Viewer cannot obtain the list of available historical aggregates from the server; it displays a static list.

OPC UA

 

10445

The initial setup of Azure Active Directory Security may break the ability to load GraphWorX displays in HTML5.

GraphWorX

To fix this, add a default group and allow all files.

10788

The HTML5 display may fail to load, returning HTTP Error 500.19 - Internal Server Error.

GraphWorX

To fix the issue, try reinstalling dotnet-hosting-8.0.x-win.exe, where x is the installed or latest version.